MSR35H/HP
Documentation
- General Overview (PDF 2.66mb)
Overview
The Guardmaster® MSR35H/HP is a microprocessor-based, two-hand control monitoring safety relay, with safety-rated, solid-state outputs.
The input of the MSR35H/HP accepts two switches, each containing one normally open and one normally closed. Both switches must be actuated within 0.5 seconds of each other.
The MSR35 can alternatively be wired with two switches with normally open contacts to a Category IIIA application per EN 574.
The reset capability of the MSR35H/HP allows it to be set up for manual or automatic reset.
The outputs include two normally-open safety-rated outputs that can be connected to loads up to 2 A at 24V DC. These outputs can be used to send a safety stop signal to a machine or manufacturing system.
The MSR35H/HP also has one solid-state normally-closed auxiliary output, which must only be used to indicate the status of the MSR35H/HP
- Category 4 per EN 954-1
- Category IIIC or IIIA per EN 574
- Two solid-state safety outputs
- One solid-state auxiliary output
- Two-hand control input
Products
- MSR35H Two-Hand Control Monitoring Relays with Fixed Terminals
- MSR35HP Two-Hand Control Monitoring Relays with Removable Terminals
Certifications
- CE Marked for all applicable directives, cULus, c-Tick, and TÜV
Note: Guardmaster Safety Relays have been marketed by Rockwell Automation under the trade name "Minotaur" in the past.
Specs
| Safety Ratings | |
| Standards | EN 954-1, ISO 13849-1, EN 574, IEC/EN 60204-1, ANSI B11.19, AS4024.1 |
| Safety Classification | Cat. 4 per EN 954-1 (ISO 13849-1), SIL CL3 per EN IEC 62061, PLe per ISO 13849-1 |
| Functional Safety Data ⋆ | PFHD: < 9.2 x 10-10 |
| Note: For up-to-date information, visithttp://www.ab.com/safety/ | MTTFd: > 631 years |
| Suitable for performance levels Ple (according to ISO 13849-1:2006) and for use in SIL3 systems (according to IEC 62061) depending on the architecture and application characteristics | |
| Certifications | CE Marked for all applicable directives, cULus, c-Tick, and TÜV |
| Power Supply | |
| Input Power Entry | 24V DC SELV |
| Power Consumption | 3 W |
| Inputs | |
| Safety Inputs | 1 N.C. & 1 N.O. or 2 N.O. |
| Input Simultaneity | 0.5 s |
| Input Resistance, Max. | 200 W |
| Reset | Automatic |
| Power On Delay/ | 3 seconds/20 ms |
| Recovery Time | |
| Response Time | 15 ms |
| Outputs | |
| Safety Contacts | 2 N.O., 2 A @ 24V DC |
| Auxiliary Contacts | 1 N.O., 50 mA @ 24V DC |
| Fuses, Output | External 6 A slow blow or 10 A fast acting |
| Power LED Diagnostics | 3 s Blink: Initialization |
| Constant: Normal Operation | |
| 2 Blinks: Configuration change during operation | |
| 4 Blinks: Solid state output switch fault | |
| Continuous blinking: Internal fault | |
| Environmental and Physical Characteristics | |
| Enclosure Type Rating/ | IP40 (NEMA 1), DIN 0470/ |
| Terminal Protection | IP20, DIN 0470 |
| Operating Temperature [C (F)] | -5…+55 ° (23…131 °) |
| Vibration | 10…55 Hz, 0.35 mm |
| Shock | 10 g, 16 ms, 100 shocks |
| Mounting | 35 mm DIN Rail |
| Weight [g (lb)] | 130 (0.287) |
| Conductor Size, Max. | 0.2…2.5 mm2 (24…14 AWG) |
⋆ Usable for ISO 13849-1:2006 and IEC 62061. Data is based on the following assumptions:
- Mission time/Proof test interval of 20 years